User Manuals
Sample Programs
NR25 EtherNet/IP RSLogix 5000 sample programs
NR25 EtherNet/IP Micro850 sample programs
NR25 DeviceNet sample programs
Configuration Files
Software
EtherNet configuration software
The AMCI NR25 series of heavy-duty Networked Resolvers are compatible with all PLCs/PACs that support EtherNet/IP, Modbus-TCP, DeviceNet, or Profibus. The NR25 series networked resolvers are available in absolute single-turn and multi-turn packages using an IP67 rated 2.5" size industrial housing. Solid shaft and hub shaft styles are available to suit various mounting requirements. These networked absolute rotary resolvers provide up to 30 bit total resolution, delivering 16 bit (65536 steps) per revolution and up to an additional 14 bit (16384 revolutions) for multi-turn versions.
Easy To Configure & Install
AMCI's networked resolvers are designed for simple set-up and trouble free performance. The NR25 networked resolvers are compatible with all PLCs and PACs that support EtherNet/IP, Modbus-TCP, DeviceNet, or Profibus including Allen-Bradley and Schneider. Programmed using the PLC/PAC resident software ensures hassle free integration with your application.
The NR25 networked resolvers offer a variety of programmable features:
All programmable parameters and the preset offset are stored in the internal non-volatile memory for speedy retrieval, making it quick and easy to configure your NR25 networked resolver.
Power over Ethernet (PoE)
AMCI's NR25 EtherNet/IP resolvers come standard with Power over Ethernet (PoE), making it possible to install this resolver using a single Ethernet cable that transmits data AND power! Your connector and cabling requirements are cut in half, plus installation is simpler and less expensive. The Power over Ethernet feature allows you to use AMCI's NR25 resolver in applications where utilizing a traditional DC power supply would be inconvenient, plus all of these advantages:
NOTE:
NR25 end connector units allow customers to either use separate network and auxiliary power connections, or a single Ethernet cable/connection to transmit data and power using Power over Ethernet (PoE).
NR25 side connector units are only available with Power over Ethernet (PoE), using a single Ethernet cable to transmit data and power.
Heavy-duty Performance & Reliability
The NR25 networked resolver supplies absolute position feedback without glass discs or sensitive LED components, enabling it to withstand high levels of shock and vibration. The IP67 rated housing guarantees protection against dust and water ingress. Add the NR25 EtherNet/IP resolver's impressive shaft load ratings and ruggedness is second to none.
AMCI's NR25 networked resolver is the heavy-duty solution for single-turn and multi-turn position applications requiring serious reliability for today's harshest industrial environments.
NR25 (all networks): 16 bit Single-turn
Price | $969 - $1,115/ea
NR25 (all networks): 28 bit Multi-turn
Price | $1,205 - $1,351/ea
NR25 (all networks): 30 bit Multi-turn
Price | $1,336 - $1,482/ea
Stainless Steel Option: add to above pricing
Price | $550/ea
Note: Pricing is US Domestic only
Consult the factory for availability
Contact SalesAMCI products are uniquely designed to provide the best PLC integration available. Unlike other products that require a separate software package for configuration or operation, AMCI's PLC-based products are programmed using your PLC's software - nothing new to buy or learn!
Our expertise with the leading PLC manufacturers (e.g. Allen-Bradley Schneider, GE, etc) is unmatched when it comes to high performance Specialty I/O, Position Sensing, and Motion Control technology.
AMCI's NR25 Series is compatible with any PLC that supports these networks
The AMCI NR Series resolvers are engineered to save customers time and money. Utilizing an innovative design, this optical encoder replacement delivers reliable, heavy-duty position feedback. Several features set this family of rotary encoders apart from the competition; namely, its cost saving durability, field programmability, and wide range of applications.
NR25 Networked Resolver | |
---|---|
Package style: | 2.5" diameter housing available with flange, servo, or hub shaft mounting |
Housing: | Powder coated aluminum housing or stainless steel |
Shaft sizes: | Solid shaft diameter 1/4 (single-turn only) , 3/8", 5/8”, or 10 mm diameter stainless steel Hub shaft inner diameter 1/2” standard inner diameter stainless steel shaft 3/8", 1/2", 10mm, and 12mm bore reducers |
Shaft loading: | Solid shaft: 1/4", 3/8", and 10mm shafts: 40 lbs. radial/20 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. 5/8" shaft: 100 lbs. radial/50 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts: 40 lbs. radial/20 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. |
Starting torque: | Solid shaft: 1/4”, 3/8”, & 10mm shafts = 2.0 oz-in max @25° C 5/8” shaft = 6.0 oz-in max @25° C Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts = 6.0 oz-in max @25° C |
Moment of inertia: | Solid shaft: 1/4", 3/8", & 10 mm shafts = 6.00 x 10-4 oz-in-sec2 5/8" shaft = 8.50 x 10-4 oz-in-sec2 Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts = 8.50 x 10-4 oz-in-sec2 |
Connector location: | End connector version: 2 connectors (1 connector) for data or data/power when using Power over Ethernet (PoE) (1 connector) for auxiliary power if not using PoE feature Side connector version: 1 connector - PoE ONLY (1 connector) transmits data and power via Power over Ethernet (PoE) |
NR25 Networked Resolver | |
---|---|
Package style: | 2.5" diameter housing available with flange, servo, or hub shaft mounting |
Housing: | Powder coated aluminum housing or stainless steel |
Shaft sizes: | Solid shaft diameter 1/4 (single-turn only) , 3/8", 5/8”, or 10 mm diameter stainless steel Hub shaft inner diameter 1/2” standard inner diameter stainless steel shaft 3/8", 1/2", 10mm, and 12mm bore reducers |
Shaft loading: | Solid shaft: 1/4", 3/8", and 10mm shafts: 40 lbs. radial/20 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. 5/8" shaft: 100 lbs. radial/50 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts: 40 lbs. radial/20 lbs. axial maximum shaft loading. Bearing life rated at 2X109 revolutions minimum at maximum shaft load. |
Starting torque: | Solid shaft: 1/4”, 3/8”, & 10mm shafts = 2.0 oz-in max @25° C 5/8” shaft = 6.0 oz-in max @25° C Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts = 6.0 oz-in max @25° C |
Moment of inertia: | Solid shaft: 1/4", 3/8", & 10 mm shafts = 6.00 x 10-4 oz-in-sec2 5/8" shaft = 8.50 x 10-4 oz-in-sec2 Hub shaft: 3/8", 1/2", 10mm, and 12mm shafts = 8.50 x 10-4 oz-in-sec2 |
Connector location: | End connector version: 2 connectors (1 connector) for data or data/power when using Power over Ethernet (PoE) (1 connector) for auxiliary power if not using PoE feature Side connector version: 1 connector - PoE ONLY (1 connector) transmits data and power via Power over Ethernet (PoE) |
Power Connector
Pin | Signal | Explanation |
1 | No Connection | - |
2 | +Vdc | 12 to 54Vdc |
3 | No Connection | - |
4 | Common | - |
Pin | Signal | Explanation |
1 | No Connection | - |
2 | +Vdc | 12 to 54Vdc |
3 | No Connection | - |
4 | Common | - |
Data/PoE Connector
Pin | Signal | Explanation |
1 | Tx+ | White / Orange |
2 | Rx+ | White / Green |
3 | Tx- | Orange |
4 | RX- | Green |
Pin | Signal | Explanation |
1 | Tx+ | White / Orange |
2 | Rx+ | White / Green |
3 | Tx- | Orange |
4 | RX- | Green |
CON1 Power Connector
Standard A-coded 4-pin M12 male connector
(e.g. Binder P/N 09-3431-00-04)
Pin | Signal |
1 | +24Vdc (10 to 30Vdc) |
2 | No Connection |
3 | DC Common |
4 | No Connection |
Pin | Signal |
1 | +24Vdc (10 to 30Vdc) |
2 | No Connection |
3 | DC Common |
4 | No Connection |
CON2 BUS OUT Data Connector
Standard B-coded 5-pin M12 female connector
(e.g. Binder P/N 09-4442-00-05 or Phoenix P/N 1515044)
Pin | Signal |
1 | BUS_VDC isolated |
2 | BUS-A line (green) RxD/TxD-N |
3 | BUS_GND isolated |
4 | BUS-B line (red) RxD/TxD-P |
5 | No Connection |
Pin | Signal |
1 | BUS_VDC isolated |
2 | BUS-A line (green) RxD/TxD-N |
3 | BUS_GND isolated |
4 | BUS-B line (red) RxD/TxD-P |
5 | No Connection |
CON3 BUS IN Data Connector
Standard B-coded 5-pin M12 male connector
(e.g. Binder P/N 09-4441-00-05)
Pin | Signal |
1 | No Connection |
2 | BUS-A line (green) RxD/TxD-N |
3 | No Connection |
4 | BUS-B line (red) RxD/TxD-P |
5 | No Connection |
Pin | Signal |
1 | No Connection |
2 | BUS-A line (green) RxD/TxD-N |
3 | No Connection |
4 | BUS-B line (red) RxD/TxD-P |
5 | No Connection |
BUS IN & Power Connector
Pin | Signal | Explanation |
1 | See Note 1 | Shield Drain |
2 | +Voltage | Red |
3 | -Voltage | Black |
4 | CAN_H | White |
5 | CAN_L | Blue |
Pin | Signal | Explanation |
1 | See Note 1 | Shield Drain |
2 | +Voltage | Red |
3 | -Voltage | Black |
4 | CAN_H | White |
5 | CAN_L | Blue |
BUS OUT & Power Connector
Pin | Signal | Explanation |
1 | See Note 1 | Shield Drain |
2 | +Voltage | Red |
3 | -Voltage | Black |
4 | CAN_H | White |
5 | CAN_L | Blue |
Pin | Signal | Explanation |
1 | See Note 1 | Shield Drain |
2 | +Voltage | Red |
3 | -Voltage | Black |
4 | CAN_H | White |
5 | CAN_L | Blue |
NOTE #1) Pin 1 on the Bus In and Bus Out connectors are internally connected to each other and are connected to the body of the NR25 through a 2 nF capacitor.
NR25 Networked Resolver | |
---|---|
Enclosure: | IP67 (valid only with working shaft seal & mating connector fitted) |
Shock: | 50 G's for 11 mSec |
Vibration: | 20 g, 5 to 2,000 Hz |
Operating temperature: | -40° C to 85° C standard |
NR25 Networked Resolver | |
---|---|
Enclosure: | IP67 (valid only with working shaft seal & mating connector fitted) |
Shock: | 50 G's for 11 mSec |
Vibration: | 20 g, 5 to 2,000 Hz |
Operating temperature: | -40° C to 85° C standard |
NR25 Networked Resolver | |
---|---|
Output Code: | EtherNet/IP, Modbus-TCP, Profibus-DP, or DeviceNet |
Resolution: | Single Turn = 65536 counts max Multi Turn = (2 versions) 65536 counts / turn & 4096 turns maximum 65536 counts / turn & 16384 turns maximum |
Direction of Increasing Counts: | Programmable over the network default = CW increasing looking at the shaft |
Programmable Parameters: | -Direction of Increasing Counts -Counts Per Turn -Velocity Units -Preset Function -Total Measurement Range (defines the number of counts where the position rolls over to zero) |
Time Stamp: | Time stamp is an unsigned double integer value with an interval of 400 nanoseconds; rolls over every 1717.9869184 seconds. |
Power requirements (including PoE): | --EtherNet/IP & Modbus-TCP-- 12 to 54Vdc 2.5 W maximum 100mA @ 24Vdc --Profibus-DP-- 10 to 30Vdc 1.32 W maximum 55mA @ 24Vdc --DeviceNet-- 11 to 25Vdc 1.5 W maximum 50mA @ 24Vdc |
NR25 Networked Resolver | |
---|---|
Output Code: | EtherNet/IP, Modbus-TCP, Profibus-DP, or DeviceNet |
Resolution: | Single Turn = 65536 counts max Multi Turn = (2 versions) 65536 counts / turn & 4096 turns maximum 65536 counts / turn & 16384 turns maximum |
Direction of Increasing Counts: | Programmable over the network default = CW increasing looking at the shaft |
Programmable Parameters: | -Direction of Increasing Counts -Counts Per Turn -Velocity Units -Preset Function -Total Measurement Range (defines the number of counts where the position rolls over to zero) |
Time Stamp: | Time stamp is an unsigned double integer value with an interval of 400 nanoseconds; rolls over every 1717.9869184 seconds. |
Power requirements (including PoE): | --EtherNet/IP & Modbus-TCP-- 12 to 54Vdc 2.5 W maximum 100mA @ 24Vdc --Profibus-DP-- 10 to 30Vdc 1.32 W maximum 55mA @ 24Vdc --DeviceNet-- 11 to 25Vdc 1.5 W maximum 50mA @ 24Vdc |
The following mating connectors are available from AMCI
--- EtherNet/IP, Modbus-TCP, Profibus-DP --- | |
Power Connector (on NR25 encoder) | Standard M12 A-coded 4 pin male connector such as Binder #09-3431-00-04 or equivalent |
Power Mating Connector (AMCI Part# MS-29) | Standard M12 A-coded 4 pin female connector such as Binder #99-0430-12-04 or equivalent (sold separately) |
--- Profibus-DP --- | |
Mating Connector (AMCI Part# MS-29) | Standard B-coded 5-pin M12 male connector such as Binder P/N 09-4441-00-05 |
--- EtherNet/IP, Modbus-TCP, Profibus-DP --- | |
Power Connector (on NR25 encoder) | Standard M12 A-coded 4 pin male connector such as Binder #09-3431-00-04 or equivalent |
Power Mating Connector (AMCI Part# MS-29) | Standard M12 A-coded 4 pin female connector such as Binder #99-0430-12-04 or equivalent (sold separately) |
--- Profibus-DP --- | |
Mating Connector (AMCI Part# MS-29) | Standard B-coded 5-pin M12 male connector such as Binder P/N 09-4441-00-05 |
--- EtherNet/IP & Modbus-TCP (Data/PoE) --- | |
Connector (on NR25 encoder) | Standard M12 D-coded 4 pin female connector such as Binder #09-3732-00-04 or equivalent |
Mating Connector (AMCI Part# MS-28) | Standard M12 D-coded 4 pin male connector such as Binder #99-3729-810-04 or equivalent (sold separately) |
--- Profubus-DP --- | |
CON2 BUS OUT Connector (MS-39) | Standard B-coded 5-pin M12 female connector such as Binder P/N 09-4442-00-05 --- or --- Phoenix P/N 1515044 |
CON BUS IN Connector (AMCI Part# MS-38) | Standard B-coded 5-pin M12 male connector such as Binder P/N 09-4441-00-05 |
--- DeviceNet --- | |
AMCI part #MS-31 (mating connector to NR25 encoder BUS IN) | Standard M12 A-coded 5 pin female connector such as Binder #99-0436-12-05 (straight) or equivalent (sold separately) Binder #99-0436-52-05 (right angle) or equivalent (sold separately) |
AMCI part #MS-32 (mating connector to NR25 encoder BUS OUT) | Standard M12 A-coded 5 pin male connector such as Binder #99-0437-12-05 (straight) or equivalent (sold separately) Binder #99-0437-52-05 (right angle) or equivalent (sold separately) |
--- EtherNet/IP & Modbus-TCP (Data/PoE) --- | |
Connector (on NR25 encoder) | Standard M12 D-coded 4 pin female connector such as Binder #09-3732-00-04 or equivalent |
Mating Connector (AMCI Part# MS-28) | Standard M12 D-coded 4 pin male connector such as Binder #99-3729-810-04 or equivalent (sold separately) |
--- Profubus-DP --- | |
CON2 BUS OUT Connector (MS-39) | Standard B-coded 5-pin M12 female connector such as Binder P/N 09-4442-00-05 --- or --- Phoenix P/N 1515044 |
CON BUS IN Connector (AMCI Part# MS-38) | Standard B-coded 5-pin M12 male connector such as Binder P/N 09-4441-00-05 |
--- DeviceNet --- | |
AMCI part #MS-31 (mating connector to NR25 encoder BUS IN) | Standard M12 A-coded 5 pin female connector such as Binder #99-0436-12-05 (straight) or equivalent (sold separately) Binder #99-0436-52-05 (right angle) or equivalent (sold separately) |
AMCI part #MS-32 (mating connector to NR25 encoder BUS OUT) | Standard M12 A-coded 5 pin male connector such as Binder #99-0437-12-05 (straight) or equivalent (sold separately) Binder #99-0437-52-05 (right angle) or equivalent (sold separately) |
Data Cord Sets: | --- EtherNet/IP & Modbus-TCP, Profibus-DP --- Phoenix #1569391, #1569401, #1569414, #1569427, or equivalent. (sold separately) --- DeviceNet --- Can be purchased from the following manufacturers: Phoenix Contact: www.phoenixcontact.com Turck Inc: www.turck-usa.com Lumberg Automation: www.lumberg-automationusa.com |
Power Cord Sets: | --- EtherNet/IP & Modbus-TCP, Profibus-DP --- Phoenix #1536308 or equivalent (sold separately) |
Cables: | --- DeviceNet --- Can be purchased from the following manufacturers: Belden Inc: www.belden.com Phoenix Contact: www.phoenixcontact.com |
Data Cord Sets: | --- EtherNet/IP & Modbus-TCP, Profibus-DP --- Phoenix #1569391, #1569401, #1569414, #1569427, or equivalent. (sold separately) --- DeviceNet --- Can be purchased from the following manufacturers: Phoenix Contact: www.phoenixcontact.com Turck Inc: www.turck-usa.com Lumberg Automation: www.lumberg-automationusa.com |
Power Cord Sets: | --- EtherNet/IP & Modbus-TCP, Profibus-DP --- Phoenix #1536308 or equivalent (sold separately) |
Cables: | --- DeviceNet --- Can be purchased from the following manufacturers: Belden Inc: www.belden.com Phoenix Contact: www.phoenixcontact.com |
AMCI’s wide selection of resolver transducers, resolver interfaces for PLC based systems, and related accessories provide a complete, quality solution supported by over 25 years of product design, manufacturing, and application experience. Watch the video to learn more about these maximum duty rotary sensors!
Duration 01:20
AMCI makes buying PLC-based automation easy...our sales group will help you:
Contact AMCI Sales today:
860-585-1254
AMCI's sales team takes the hassle out of placing your order. We'll advise on product selection, alternatives, lead times, and present you with point of purchase options. Call (860) 585-1254 or email AMCI sales today!
Generate your NR25 series networked resolver part number by using this helpful ordering guide. Starting from left to right, use the following diagram and table to choose the desired options. Each gray box must contain a single alphanumeric character. Please note the following…
Part Number Character | NR25 Networked Resolver | Most Popular Selections |
---|---|---|
Mounting style: | F = 2.65" square flange S = 2.5" diameter servo mount (unavailable w/ the 5/8” shaft option) H = Hub shaft | F (Square flange) |
Shaft Seal Type & Housing Material: | A=Nitrile seal, stainless steel housing B=Nitrile seal, aluminum housing C=Viton seal, stainless steel housing V=Viton seal, aluminum housing | B (Nitrile seal) |
Shaft Diamter: (must choose either solid or hub shaft) | Solid shaft option (Flange mount only) 1 = 3/8" diameter 0.875” length, No Flat 2 = 10mm diameter 0.875” length, No Flat 3 = 1/4" diameter 0.875” length, No Flat 4 = 6mm diameter 10mm length, w/Flat 5 = 5/8" diameter 1.30” length, w/Keyway 6 = 10mm diameter 20mm length, w/Flat --- Hub shaft option 1 = 3/8" inner diameter 1.1” max. depth 2 = 10mm inner diameter 1.1” max. depth 4 = 1/2" inner diameter 1.1” max. depth 6 = 12mm inner diameter 1.1” max. depth | 1 (3/8" shaft) --or-- 4 (1/2" inner diameter) |
Interface Type: | E = Ethernet interface (EtherNet/IP & Modbus TCP) B = Serial interface (Profibus or DeviceNet) | E, B Both types readily available |
Output Configuration: | 1 = 16 Bit Single Turn (65536 counts/turn) 2 = 28 Bit Multi Turn (65536 counts/turn & 4,096 turns) 3 = 30 Bit Multi Turn (65536 counts/turn & 16384 turns) | 2 (Multi-turn) |
Output Code: | A = EtherNet/IP P = Profibus-DP D = DeviceNet | A, P, D All types readily available |
Connector Location: | --Ethernet interface-- E04 = End (2 connectors) 1 connector for data or data/power (Power over Ethernet - PoE) 1 connector for auxiliary power if not using PoE feature S02 = Side (1 connector) 1 connector transmits data and power via Power over Ethernet (PoE) --Profibus interface-- E04 = End (3 connectors) 1 connector for bus in 1 connector for bus out 1 connector for aux power --DeviceNet-- E02 = End (2 connectors) each connector supplies data & power E01 = End (1 connector) 1 connector supplies data & power | E04 (End Connector) --DeviceNet-- E02 |
Part Number Character | NR25 Networked Resolver | Most Popular Selections |
---|---|---|
Mounting style: | F = 2.65" square flange S = 2.5" diameter servo mount (unavailable w/ the 5/8” shaft option) H = Hub shaft | F (Square flange) |
Shaft Seal Type & Housing Material: | A=Nitrile seal, stainless steel housing B=Nitrile seal, aluminum housing C=Viton seal, stainless steel housing V=Viton seal, aluminum housing | B (Nitrile seal) |
Shaft Diamter: (must choose either solid or hub shaft) | Solid shaft option (Flange mount only) 1 = 3/8" diameter 0.875” length, No Flat 2 = 10mm diameter 0.875” length, No Flat 3 = 1/4" diameter 0.875” length, No Flat 4 = 6mm diameter 10mm length, w/Flat 5 = 5/8" diameter 1.30” length, w/Keyway 6 = 10mm diameter 20mm length, w/Flat --- Hub shaft option 1 = 3/8" inner diameter 1.1” max. depth 2 = 10mm inner diameter 1.1” max. depth 4 = 1/2" inner diameter 1.1” max. depth 6 = 12mm inner diameter 1.1” max. depth | 1 (3/8" shaft) --or-- 4 (1/2" inner diameter) |
Interface Type: | E = Ethernet interface (EtherNet/IP & Modbus TCP) B = Serial interface (Profibus or DeviceNet) | E, B Both types readily available |
Output Configuration: | 1 = 16 Bit Single Turn (65536 counts/turn) 2 = 28 Bit Multi Turn (65536 counts/turn & 4,096 turns) 3 = 30 Bit Multi Turn (65536 counts/turn & 16384 turns) | 2 (Multi-turn) |
Output Code: | A = EtherNet/IP P = Profibus-DP D = DeviceNet | A, P, D All types readily available |
Connector Location: | --Ethernet interface-- E04 = End (2 connectors) 1 connector for data or data/power (Power over Ethernet - PoE) 1 connector for auxiliary power if not using PoE feature S02 = Side (1 connector) 1 connector transmits data and power via Power over Ethernet (PoE) --Profibus interface-- E04 = End (3 connectors) 1 connector for bus in 1 connector for bus out 1 connector for aux power --DeviceNet-- E02 = End (2 connectors) each connector supplies data & power E01 = End (1 connector) 1 connector supplies data & power | E04 (End Connector) --DeviceNet-- E02 |
NR25 Networked Rotary Encoder - Single-turn & Multi-turn absolute encoders up to 30 bit res...
PDF DownloadWhen discussing resolvers, people often interchange terms such as: encoders, rotary position se...
Read the TutorialMatt Tellier presents this 15 minute tutorial on the role that IP Ratings play in specifying au...
Watch Now